System Oil Stabilization
- Prior to opening the refrigerant system for repairs (except compressor seizure) the system must be stabilized for correct oil replenishment.
- Follow these procedures:
- Engine speed set to 1,500 rpm
- A/C "ON"
- Air source to recirculate
- Blower 4th or high speed position
- Make sure the air entering the evaporator is above 26.7°C (80°F).
- The discharge (high) side pressure must be above 588 kPa (6 kg/cm2 , 85 psi).
- Operate the A/C for 10 minutes.