Pinpoint Test X : The RHVAC Module Does Not Respond To The Scan Tool
WARNING: This page is about a different car, the 2018 Lincoln MKT. However, it is still accessible from the selected car via links, so may be relevant.
NOTE:
Failure to disconnect the battery when instructed will result in false resistance readings. Refer to Battery, Mounting and Cables
.
- X1 CHECK THE RHVAC MODULE VOLTAGE SUPPLY CIRCUITS FOR AN OPEN
- Ignition OFF.
- Disconnect: RHVAC Module C3198 .
- Ignition ON.
- Measure the voltage
between:
Positive Lead Negative Lead Pin Circuit Pin Circuit C3198-6 SBP06 (BN/RD) - Ground
Are the voltages greater than 11 volts?
Yes GO to X2. No VERIFY the Body Control Module (BCM) fuse 6 (5A) is OK. If OK, REPAIR the circuit. If not OK, REFER to the OEM ELECTRICAL WIRING DIAGRAM INTRODUCTION to identify the possible causes of the circuit short. - X2 CHECK THE RHVAC MODULE GROUND CIRCUITS FOR AN OPEN
- Ignition OFF.
- Disconnect: Negative Battery Cable.
- Measure the resistance
between:
Positive Lead Negative Lead Pin Circuit Pin Circuit C3198-5 GD374 (BK/WH) - Ground
Are the resistances less than 3 ohms?
Yes GO to X3. No REPAIR the circuit. - X3 CHECK THE MS-CAN CIRCUITS BETWEEN THE RHVAC MODULE AND THE DLC FOR AN OPEN
- Disconnect: RHVAC Module C3198 .
- Measure the resistance
between:
Positive Lead Negative Lead Pin Circuit Pin Circuit C3198-1 VDB06 (GY/OG) C251-3 VDB06 (GY/OG) C3198-2 VDB07 (VT/OG) C251-11 VDB07 (VT/OG)
Are the resistances less than 3 ohms?
Yes GO to X4. No REPAIR the circuit in question. - X4 CHECK FOR CORRECT RHVAC MODULE OPERATION
- Disconnect all the RHVAC module connectors.
- Repair:
- corrosion (replace connector or terminals - clean module pins)
- damaged or bent pins - replace terminals/pins
- pushed-out pins - replace pins as necessary
- Connect all the RHVAC module connectors and make sure they seat correctly.
- Operate the system and verify the concern is still present.
Is the concern still present?
Yes CHECK OASIS for any applicable TSBs. If a TSB exists for this concern, discontinue this test and follow TSB instructions. If no TSBs address this concern, INSTALL a new RHVAC module. REFER to Auxiliary Climate Control . No The system is operating correctly at this time. The concern may have been caused by a loose or corroded connector. ADDRESS the root cause of any connector or pin issues.