Inspection Procedure
- CHECK AIR CONDITIONING AMPLIFIER
- Remove the A/C amplifier with the connectors still connected.
- Turn the ignition switch ON.
- Measure the voltage between terminals TAM (A48-7) and FRSG (A48-18) of the A/C amplifier connector at each temperature.
Standard voltage:
1.35 to 1.75 V at 25 °C (77°F)
0.85 to 1.25 V at 40 °C (104°F)
HINT:
- As the temperature increases, the voltage decreases.
- However, if DTC 12 is displayed, check and replace the A/C amplifier.
OK: REPLACE AIR CONDITIONING AMPLIFIER
NG: Go to next step
- INSPECT AMBIENT TEMPERATURE SENSOR
- Disconnect the A1 ambient temperature sensor connector.
- Measure the resistance between terminals 1 and 2 of the ambient temperature sensor connector at each temperature.
Standard resistance:
1.6 to 1.8 kΩ at 25°C (77°F)
0.5 to 0.7 kΩ at 40 °C (104°F)
HINT:
As the temperature increases, the resistance decreases.
NOTE: When installing the ambient temperature sensor, be sure to connect the sensor connector before connecting the battery.
NG: REPLACE AMBIENT TEMPERATURE SENSOR
Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002
OK: Go to next step
- CHECK WIRE HARNESS (AIR CONDITIONING AMPLIFIER - AMBIENT TEMPERATURE SENSOR)
NG: REPAIR OR REPLACE HARNESS AND CONNECTOR
OK: REPLACE AIR CONDITIONING AMPLIFIER