Evacuating A/C System
- Close both valves on manifold gauge set. Connect manifold gauge set to high and low side service valves. See SERVICE VALVE LOCATIONS in this article. Connect a hose to center connector on manifold gauge set and evacuation pump.
- Open both valves on manifold gauge set. Start evacuation pump and operate until low side vacuum reading of at least 25 in. Hg is obtained.
- Continue operating evacuation pump for 15 minutes. If compressor, evaporator, refrigerant line, etc. have been replaced, operate evacuation pump for at least 30 minutes.
- Close both valves on manifold gauge set. Turn off evacuation pump. Observe low side gauge. If vacuum reading drops in 5 minutes, system has leak. Perform leak testing procedure and repair.