Charging A/C System
NOTE:
See A/C SYSTEM SPECS in the AIR CONDITIONING section for system capacities. Manufacturer does not recommend using one pound cans. Using a charging station will allow precise measurement of R-12 charge.
- System must be evacuated before charging. With manifold gauge set attached from evacuation procedures, attach R-12 container to hose on center connector of manifold gauge set. Fully open R-12 container valve and purge air from center hose.
- Disconnect electrical connector from clutch cycling pressure switch, located on the accumulator. Install jumper wire between connector terminals.connector.
- Open low side valve on manifold gauge set and allow R-12 to enter system. When no more R-12 is being drawn into system, start and run engine. Place A/C-heater controls on MAX cold position with blower speed on high.NOTE: In high temperature areas, it may be necessary to operate a high volume fan to blow air through condenser and radiator.
- When proper amount of R-12 has been added, close low side valve on manifold gauge set. Remove jumper wire and connect clutch cycling pressure switch. Reinstall electrical connector.
- Operate system to verify proper operation and normal system pressures. Disconnect manifold gauges set. Install service port caps. Check system for leaks.