Dye Solution Leak Testing Procedures
The following procedure is for introducing a dye solution, not dye-charged refrigerant, into A/C system.
1) Connect manifold gauge set to air conditioning system in a normal manner. Remove center hose from manifold gauge set, and replace it with a short piece (6" long) of 1/4" tubing using two 1/4" flare nuts. Connect a container of dye solution to the tubing.
2) Connect one end of gauge set center hose to dye solution container. Connect a container of refrigerant to the other end of the hose. Operate engine at idle speed. Set the air conditioning system for maximum cooling. Slowly open the low-side hand valve to allow the dye solution to enter the system.
3) Charge the system to at least 50 percent capacity. Operate the system for 15 minutes, and then shut off both the air conditioning system and the engine. Check all connections for signs of the colored dye solution. Check the vehicle again 24 hours later. If leaks are found, repair as necessary.