Cold Start Arrest
IHKA E36 also includes an automatically activated cold start arrest function. The control panel/ module checks for the necessary conditions at engine start-up:
- IHKA system turned "on" and
- Maximum defrosting request is not present and
- Left Y-factor is 100% (maximum heating required) and
- Left side "AUTO" mode request is present and
- Left heater core temperature is less than 68°F (20°C).
If these conditions exist, the control panel/module will:
- Open the defroster flaps and
- Close all other air distribution flaps and
- Operate the blower motor, A/C compressor, fresh air flaps, and recirc. air flaps according to control panel/module settings .
When the left heater core temperature reaches 68°F (20°C), cold start arrest ends and all IHKA system functions depend upon control panel/module settings and sensed conditions.